Make the best use of Scientific Research and information from our 700+ peer reviewed, Open Access Journals that operates with the help of 50,000+ Editorial Board Members and esteemed reviewers and 1000+ Scientific associations in Medical, Clinical, Pharmaceutical, Engineering, Technology and Management Fields.
Meet Inspiring Speakers and Experts at our 3000+ Global Conferenceseries Events with over 600+ Conferences, 1200+ Symposiums and 1200+ Workshops on
Medical, Pharma, Engineering, Science, Technology and Business

Novel Loss-Voltage Sensitivity Factor for Capacitor Placement in Radial Distribution System Using Analytical Approach

Ahmed R. Abul’Wafa*

Ain-Shams University, Electric Power and Machines, Cairo, Egypt

*Corresponding Author:
Ahmed R. Abul‘Wafa
Ain-Shams University
Electric Power and Machines
Cairo, Egypt
Tel: +20226831474
E-mail: Ahmedlaila.nelly.ola@gmail.com

Received Date: January 21, 2016; Accepted Date: February 20, 2017; Published Date: February 27, 2017

Citation: Abul’Wafa AR (2017) Novel Loss-Voltage Sensitivity Factor for Capacitor Placement in Radial Distribution System Using Analytical Approach. J Electr Electron Syst 6:213. doi:10.4172/2332-0796.1000213

Copyright: © 2017 Abul’Wafa AR. This is an open-access article distributed under the terms of the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original author and source are credited.

Visit for more related articles at Journal of Electrical & Electronic Systems

Abstract

An analytical technique is proposed for allocation of shunt capacitor bank in radial distribution system. The objective is formulated to determine the size, number and location of capacitor bank for real and reactive power loss reduction, voltage profile enhancement and annual cost saving. A novel Loss-Voltage Sensitivity Factor (LVSF), has been incorporated in the technique. The value of LVSF decides the candidate bus location. The achievability of the proposed method (PM) has been demonstrated on IEEE-69 bus test system allowing comparing results with latest optimization techniques in literature. Further application of PM on 130 bus relatively large distribution system shows the effectiveness and robustness of the proposed technique. Capacitors allocated (size and location) during light loading condition simulation are forced as fixed capacitors in nominal and heavy loading simulations. This development is essential when allocated capacitors in nominal and heavy loading simulations do not include nodes of fixed capacitors.

Keywords

Shunt fixed and switchable capacitor bank; Analytical approach; Distribution system; LVSF; Load flow

Introduction

Placement of capacitor of optimal sizes and at optimal locations not only reduces the power losses, but also improves the voltage stability of the electric power systems. Several meta-heuristic techniques have been used by scientists and researchers over the years to address the problems of capacitor placements. They are very effective and powerful in comparison with conventional methods in solving complex nonlinear constrained optimization problems. Authors [1], used Differential Evolution algorithm, Direct Search Algorithm [2], Artificial bee colony algorithm (ABC) [3], Flower Pollination Algorithm [4], Bacteria Foraging (BF) [5], Ant Colony Search Algorithm (ACO) [6], Cuckoo Search Algorithm (CSA) [7], Harmony Search (HS) [8], Plant Growth Simulation Algorithm (PGSA) [9], Teaching Learning Based Optimization (TLBO) [10], Firefly Algorithm (FA) [11], shark smell optimization algorithm [12], Particle Swarm Optimization (PSO) [13,14], Heuristic Algorithm [15], Fuzzy–GA method [16], Simulated Annealing (SA) [17], Genetic Algorithm (GA) [18], Nonlinear Programming [19]. Carpinelli et al. [20] solved the problem of shunt capacitor placement and sizing by approximate power flow method. S Mandal et al. [21] used a new hybrid particle swarm optimization algorithm to determine the best location and size of capacitor units in radial distribution system. The cost of real power losses and cost of capacitors were included in the objective function. However, one of the major difficulties for these methods is the premature convergence.

In this paper a new analytical method has been presented to solve the capacitor allocation problem in distribution system. The objective was formulated to minimize real power loss to its minimum value. A new Loss-Voltage Sensitivity Factor (LVSF), has been proposed here. LVSF incorporated real power loss and voltage of the system. The proposed technique gives best location and size of capacitor banks simultaneously. The efficacy of the proposed methodology has been tested on IEEE 69 bus distribution system. Three loading conditions (Light, Nominal and Heavy) are also considered here.

A further development of the proposed technique, capacitors allocated (size and location) during light loading condition simulation are forced as fixed capacitors in nominal and heavy loading simulations. This development is when allocated capacitors in nominal and heavy loading simulations do not include nodes of fixed capacitors.

The results of proposed technique applied on IEEE 69 bus distribution system are compared with various algorithms to check its supremacy. Further the proposed technique was applied on relatively large 130 bus real distribution system insuring the effectiveness and robustness of the proposed technique.

Paper Contributions

The main contributions of this paper can be defined as

• Proposal of a new technique to solve capacitor location problem especially for large scale system.

• Proposal of a new Loss-Voltage Sensitivity Factor (LVSF), has been incorporated in the technique to decide the candidate bus location.

• The proposed technique outlasts other algorithms in solving the optimal locations and sizing of capacitors in distribution systems. Moreover, it provides a promising and preferable performance over other algorithms in terms of voltage profiles, active and reactive power losses, total cost and net saving.

• Capacitor allocated (size and location) during light loading condition simulation are forced as fixed capacitors in nominal and heavy loading simulations. Capacitors determined in nominal and heavy loading simulations are switchable capacitors.

Computation Algorithm

Following pseudo code summaries the computational process for proposed analytical technique:

While Equation continue decreasing.

Do until a capacitor is allocated

a) Set any size (5 kVAr) of capacitor unit at a bus and run load flow program [22].

Calculate the Equation of the system and LVSF values for each bus.

b) Increment the size of capacitor in 5 kVAr steps and repeat ‘i’ and ‘ii’.

Store the size of capacitor which gives least amount Equation of the system.

Store the bus, which has least LVSF value, will be the best location of capacitor unit.

Repeat steps ‘d’ to ‘e’ to find more locations and sizes of capacitors as multi-capacitor compensation.

End do.

Print best capacitor placement.

Print Equation , Equation , power loss reduction % , and annual $ Saving.

Apply this process for Light loading condition to determine best location and size of fixed capacitors. Next apply this process with allocated fixed capacitors, for nominal and peak loading conditions to determine best location and size of switched capacitors.

Algorithm Variables

The variables in the computation algorithm are defined mathematically as follows:

Equation (1)

Where

Equation

Equation (2)

Operational Constraints

The operating constraints are:

• The voltage of each bus must be maintained between specified limits.

Equation (3)

• The total reactive power injected is not to exceed the total reactive power demand in radial distribution system.

• The reactive power injection at each candidate bus is given by its minimum and maximum compensation limit.

Loss-Voltage Sensitivity Factor (LVSF)

The analytical method incorporating a Loss-Voltage Sensitivity Factor (LVSF), has been proposed to determine the size and location of capacitor units. The LVSF takes the system active power loss with and without capacitors and voltage limits of individual buses with capacitors in account and suggest the best location of the capacitor. The LVSF includes main objectives (power loss reduction and voltage profile enhancement).

Equation (4)

where,

Equation Base case real power loss (kW)

Equation Real power loss after capacitor placement at a bus (kW)

Equation Per unit maximum bus voltage after capacitor placement at a bus

Equation Per unit minimum bus voltage after capacitor placement at a bus

Test Results

In proposed analytical approach, capacitor units are placed to minimize real power loss and to enhance voltage profile. The technique is employed on the IEEE 69 bus distribution system and on relatively large 130 bus real distribution system.

The implementation of proposed method for the best capacitor placement problem was done using version (9.0.0) R2016 a of MATLAB language on an Intel Core i7 processor running at 2.20 GHz with 7.95 GB RAM.

The values of various constant used in equation (1 to 2) are: Cost of power loss (KP) = $0.06/kwh, Cost of energy loss (Ke) = $0.06/kWh , capacitor installation cost for single unit (Ki) = $1000, Cost of per kVAr capacitor bank (Kc) = $5, maximum loss hours = 1500, discount rate (r) = 0.08, and economic life of investment (years) = 10.

From simulation results, it is learned that capacitor locations during light loading condition simulation may not repeated in nominal and heavy loading simulations. Therefore, in this paper capacitor allocated (size and location) during light loading condition simulation are forced as fixed capacitors in nominal and heavy loading simulations. Capacitors determined in nominal and heavy loading simulations are switchable capacitors. To the author knowledge this approach was not tackled in previous publications. This approach shall be detailed in the following section.

Case 1: 69 bus system

The IEEE 69 bus has 12.66 kV and 100 MVA base values. The base case real power loss and minimum bus voltage are 224.7893 kW and 0.9092 pu [23].

Generally Capacitor bank size, location and control are determined based on reactive load curve usually approximated by a steps ladder function. In this work, three steps functions are used. Thus, calculation of energy losses requires power losses in peak (160 % of nominal load), nominal and light (50% decrement in load) load levels.

Simulation results for the three operating conditions are summarized in Table 1. The voltage profile after compensation compared to base case is shown in Figure 1 for nominal operating condition and in Figure 2 for heavy operating condition.

  Light Load (50%) Nominal Load (100%) Heavy Load (160%)
Before Capacitor Placement Power Loss (kW) 51.6150 224.7893 651.9646
Min. bus voltage (pu) 0.9567 0.9092 0.8445
After
Capacitor Placement
Capacitor Size in kVAr and location 175/17
260/50
1267/61
303/50
2111/61
357/50
Total kVAr 435 1570 2468
Power Loss (kW) 34.6352 145.9182 410.1286
Min. bus voltage (pu) 0.9680 0.9316 0.8854
  % Loss reduction 32.8969 35.0867 37.0934

Table 1: Simulation results for 69 bus system after capacitor installation.

electrical-electronic-systems-voltage-69-bus-nominal

Figure 1: Voltage profile before and after capacitor placement for 69 bus system in nominal loading condition.

electrical-electronic-systems-voltage-69-bus-heavy

Figure 2: Voltage profile before and after capacitor placement for 69 bus system in heavy loading condition.

Meaning beside (175/17+260/50 kVAr/node) fixed capacitors, (1267/61+303/50 kVAr/node) switched capacitors are required at nominal load operating condition and additional (844/61+54/50 kVAr/node) switched capacitors are required at heavy load operating condition.

The results of proposed method are compared with latest optimization technique like Fuzzy-GA [16], Direct Search Algorithm [2], PSO [13], Heuristic [15], and Flower Pollination Algorithm [24]. The comparative analysis is shown in Table 2. It is noticed from table that the proposed approach give maximum loss reduction on lesser size of capacitor bank and percentage saving in cost exceeds those in other technique. The bus voltage profile of 69 bus system is also improved due to proposed approach. DE [2] and FPA [24] searched lesser size of capacitor bank, however resulting in lower loss reduction and percentage saving.

Items Un-compensated Compensated
Fuzzy-GA [16] DE [2] PSO [13] Heuristic [15] FPA [24] Proposed Method
Total losses (kW) 224.8949 156.62 151.3763 152.48 148.48 150.28 145.9182(Base kW losses 224.7893)
Loss reduction (%)   30.4 32.7 32.2 34 35.2 33.20 35.0867
Minimum voltage 0.9092 0.9369 0.9311   0.9305 0.9323 0.9316
Optimal location and size in kVAr (Node/kVAr)   59/100
61/700
64 800
57/150
58/50
61/1000
60/150
59/100
46/241
47/365
50/1015
8/600
58/150
60/1050
61/1350 61/1267
50/303
Total kVAr   1600 1450 1621 1800 1350 1570
Annual cost ($/year) 118,204.8 90119.5 88913.4 88006.5 86441.1 85356.7  
Net saving ($/year)   28085.3 29291.4 30198.3 31763.7 32848.1 39327.5791(Base Annual cost=128130 $/yr.)
% saving   23.8 24.8 25.6 26.9 27.8 30.69

Table 2: Comparison of annual loss saving for various techniques at nominal load for 69 bus system.

Case 2: 130 bus system

The system under consideration is 11 kV, 130 bus radial distribution system. The system load is 1911.6 kW and 1423.8 kVAr. The line and load data are given in Appendix and the tree graph of the feeder is shown in Figure 3. The real power loss of the system is 365.1864 kW and minimum bus voltage is 0.9243 pu without compensation. The procedure of proposed approach, as detailed for IEEE 69 bus system is repeated for this relatively large system to determine the best location and size of capacitor bank.

electrical-electronic-systems-tree-graph-130-bus-radial

Figure 3: Tree graph of 130 bus radial distribution system.

Simulation results for the three operating conditions are summarized in Table 3. The voltage profile after compensation compared to base case is shown in Figure 4 for nominal operating condition and in Figure 5 for heavy operating condition.

  Light Load (50%) Nominal Load (100%) Heavy Load (160%)
Before Capacitor Placement Power Loss (kW) 185.4599 365.9583 979.0706
Min. bus voltage (pu) 0.9562 0.9242 0.8760
After
Capacitor Placement
Capacitor Size in kVAr and location 10/5 1085/89
340/20
45/129
40/6
1670/89  660/19
115/128
65/3
Total kVAr 10 1510 2510
Power Loss (kW) 64.0474 241.8028 633.9606
Min. bus voltage (pu) 0.9682 0.9376 0.8992
  % Loss reduction 65.4656 33.9261 35.3367

Table 3: Simulation results of the 130 bus distribution system.

electrical-electronic-systems-voltage-130-bus-nominal

Figure 4: Voltage profile before and after capacitor placement for 130 bus system in nominal loading condition.

electrical-electronic-systems-voltage-130-bus-heavy

Figure 5: Voltage profile before and after capacitor placement for 130 bus system in heavy loading condition.

Meaning beside (10/5 kVAr/node) fixed capacitors, (1085/89+115/128+65/3 kVAr/node) switched capacitors are required at nominal load operating condition and additional (585/89+320/20+25/6 kVAr/node) switched capacitors are required at heavy load operating condition.

Conclusion

In this paper, an analytical technique is proposed for allocation of shunt capacitor bank in radial distribution system for real and reactive power loss reduction, voltage profile enhancement and annual cost saving. A new Loss-Voltage Sensitivity Factor (LVSF), has been incorporated in the technique to decide the candidate bus location.

Capacitors allocated (size and location) during light loading condition simulation are forced as fixed capacitors in nominal and heavy loading simulations. This development is when allocated capacitors in nominal and heavy loading simulations do not include nodes of fixed capacitors.

A large scale and small scale distribution systems are used to demonstrate the performance of the new formulation. The proposed algorithm provides an efficient solution since it provides a promising and preferable performance over other algorithms in terms of voltage profiles, active and reactive power losses, total cost and net saving.

References

Select your language of interest to view the total content in your interested language
Post your comment

Share This Article

Relevant Topics

Recommended Conferences

Article Usage

  • Total views: 316
  • [From(publication date):
    March-2017 - Aug 20, 2017]
  • Breakdown by view type
  • HTML page views : 271
  • PDF downloads :45
 
 

Post your comment

captcha   Reload  Can't read the image? click here to refresh

Peer Reviewed Journals
 
Make the best use of Scientific Research and information from our 700 + peer reviewed, Open Access Journals
International Conferences 2017-18
 
Meet Inspiring Speakers and Experts at our 3000+ Global Annual Meetings

Contact Us

Agri, Food, Aqua and Veterinary Science Journals

Dr. Krish

agrifoodaquavet@omicsonline.com

1-702-714-7001 Extn: 9040

Clinical and Biochemistry Journals

Datta A

clinical_biochem@omicsonline.com

1-702-714-7001Extn: 9037

Business & Management Journals

Ronald

business@omicsonline.com

1-702-714-7001Extn: 9042

Chemical Engineering and Chemistry Journals

Gabriel Shaw

chemicaleng_chemistry@omicsonline.com

1-702-714-7001 Extn: 9040

Earth & Environmental Sciences

Katie Wilson

environmentalsci@omicsonline.com

1-702-714-7001Extn: 9042

Engineering Journals

James Franklin

engineering@omicsonline.com

1-702-714-7001Extn: 9042

General Science and Health care Journals

Andrea Jason

generalsci_healthcare@omicsonline.com

1-702-714-7001Extn: 9043

Genetics and Molecular Biology Journals

Anna Melissa

genetics_molbio@omicsonline.com

1-702-714-7001 Extn: 9006

Immunology & Microbiology Journals

David Gorantl

immuno_microbio@omicsonline.com

1-702-714-7001Extn: 9014

Informatics Journals

Stephanie Skinner

omics@omicsonline.com

1-702-714-7001Extn: 9039

Material Sciences Journals

Rachle Green

materialsci@omicsonline.com

1-702-714-7001Extn: 9039

Mathematics and Physics Journals

Jim Willison

mathematics_physics@omicsonline.com

1-702-714-7001 Extn: 9042

Medical Journals

Nimmi Anna

medical@omicsonline.com

1-702-714-7001 Extn: 9038

Neuroscience & Psychology Journals

Nathan T

neuro_psychology@omicsonline.com

1-702-714-7001Extn: 9041

Pharmaceutical Sciences Journals

John Behannon

pharma@omicsonline.com

1-702-714-7001Extn: 9007

Social & Political Science Journals

Steve Harry

social_politicalsci@omicsonline.com

1-702-714-7001 Extn: 9042

 
© 2008-2017 OMICS International - Open Access Publisher. Best viewed in Mozilla Firefox | Google Chrome | Above IE 7.0 version